  Transformer Rated Capacity Calculation Method

  The rated capacity of a transformer, also known as the apparent power rating, is a crucial parameter that indicates the maximum power the transformer can deliver continuously under specified conditions without exceeding temperature limits. It is measured in volt-amperes (VA) or kilovolt-amperes (kVA). The calculation of rated capacity depends on the type of transformer (single-phase or three-phase) and involves considerations of voltage, current, and power factor.

  For single-phase transformers, the rated capacity (S) is calculated using the formula: S = V × I, where V is the rated voltage (in volts) and I is the rated current (in amperes). This formula is straightforward because single-phase transformers have a single primary and secondary winding, and the apparent power is the product of the voltage and current in either winding (since power is conserved in an ideal transformer, neglecting losses). For example, if a single-phase transformer has a secondary voltage of 240 V and a rated secondary current of 50 A, its rated capacity is 240 V × 50 A = 12,000 VA or 12 kVA.

  For three-phase transformers, the calculation is more complex due to the three-phase system. The rated capacity (S) is calculated using the formula: S = √3 × V_L × I_L, where V_L is the line-to-line rated voltage (in volts) and I_L is the line current (in amperes). The √3 factor accounts for the phase relationship in a balanced three-phase system. In a three-phase transformer, the line current is the current flowing in each line, and the line-to-line voltage is the voltage between any two lines. For instance, if a three-phase transformer has a line-to-line voltage of 480 V and a line current of 100 A, its rated capacity is √3 × 480 V × 100 A ≈ 1.732 × 480 × 100 ≈ 83,136 VA or 83.14 kVA.

  It is important to note that the rated capacity is based on the apparent power, which includes both active power (kW) and reactive power (kVAR). The active power that a transformer can deliver is affected by the power factor (PF) of the load, given by the formula: Active Power (P) = S × PF. Therefore, when selecting a transformer, the rated capacity must be sufficient to handle the apparent power requirements of the load, considering the load's power factor. For example, a 10 kVA transformer with a load power factor of 0.8 can deliver 8 kW of active power.

  Another consideration is the overload capacity of the transformer, but the rated capacity is determined based on continuous operation under normal conditions. The design of the transformer's windings, core, and cooling system must be capable of dissipating the heat generated at the rated capacity without exceeding the maximum allowable temperature rise specified by standards (such as IEC or ANSI). The temperature rise is influenced by factors such as copper losses (I²R losses in the windings) and iron losses (hysteresis and eddy current losses in the core). During the design phase, manufacturers calculate the rated capacity by ensuring that the sum of these losses results in a temperature rise within the permissible limit when the transformer is operating at full load.

  In practical applications, when calculating the required rated capacity of a transformer, it is essential to consider the total connected load, including any future expansion. The total apparent power of the load is calculated by summing the apparent power of each individual load, taking into account their power factors. A safety margin of 10-20% is often added to the calculated load to account for overloads, harmonic distortions, and future load growth. This ensures that the transformer operates within its rated capacity under normal conditions, prolonging its service life and ensuring safe and efficient operation.